Glossary · Testing, inspection and certificates

Key points

  • It measures the resistance of the insulation on all live parts of a circuit, and is also called a megger test.
  • The minimum acceptable value for the circuits in a home is 1 megohm, and a reading below that does not meet BS 7671.
  • It is one of the tests in an EICR and in the testing before a new installation is certified.
  • It is not one of the live tests. The live tests are the supply earth loop impedance, supply polarity and RCD tests.
  • It needs specialist equipment and a competent person. NICEIC says an EICR should never be a DIY job.

How an insulation resistance test works

Every cable in a home has insulation around the conductors. Over time heat, damage, moisture or poor workmanship can wear that insulation down. An insulation resistance test checks that it is still doing its job.

The IET describes it plainly. Insulation resistance testing, or megger testing as it is more commonly known, tests the resistance of the insulation of all live parts in electrical circuits. The measured value is compared with the minimum values in the standard, to verify that the insulation has not broken down through damage to cables or other parts of a circuit.[1]Institution of Engineering and Technology (IET), History of insulation resistance testing (Wiring Matters, July 2020) NICEIC lists it as one of the circuit tests in an EICR. Its purpose is to make sure all wires are properly insulated, with no risk of the insulation breaking down and causing faults or an electric shock.[2]NICEIC, Electrical Installation Condition Reports (EICRs)

The minimum value

The minimum value that BS 7671 sets for insulation resistance in a normal installation is 1 megohm. The IET traces this value back to the 17th Edition and says it is still used today.[1]Institution of Engineering and Technology (IET), History of insulation resistance testing (Wiring Matters, July 2020) It also notes that there is no documented reason for choosing 1 megohm, but that it has proved a useful starting point for judging the condition of cables and equipment.[1]Institution of Engineering and Technology (IET), History of insulation resistance testing (Wiring Matters, July 2020)

A reading under 1 megohm does not meet the requirements of the current edition. The IET says it should be given a classification code. Finding out why the value is so low takes further investigation, which the IET treats as fault-finding rather than part of the inspection itself.[3]Institution of Engineering and Technology (IET), Implications of BS 7671:2018+A4:2026 on an EICRs (Wiring Matters, July 2026) Our page on EICR observation codes explains the codes.

Item Detail
What is measured Resistance of the insulation of live parts, in megohms
Minimum value in BS 7671 1 megohm for the circuits in a home
Part of Initial testing of new work and periodic testing in an EICR
Live test No. The live tests are earth loop impedance at the supply, supply polarity and RCD testing

The IET’s list of live tests for a typical home with an RCBO on each circuit names only those three, and puts insulation resistance among the others.[4]Institution of Engineering and Technology (IET), Minimizing unnecessary live testing for initial verification (Wiring Matters, May 2025)

Example

Hannah books an EICR for her Horsforth house. The electrician tests each circuit and writes the insulation resistance for each on the schedule of test results. The lighting circuit upstairs gives a reading below the minimum. That does not meet BS 7671, so the electrician gives it a code on the report. Working out whether the cause is a damaged cable, a damp junction or a faulty fitting is a separate job that follows.[3]Institution of Engineering and Technology (IET), Implications of BS 7671:2018+A4:2026 on an EICRs (Wiring Matters, July 2026)

What people get wrong

A low insulation resistance reading is not the same as a full rewire. It tells the electrician the insulation on that circuit is not good enough, and they then need to find the reason. The cause could be one damaged part, and finding it is separate from the inspection.

People also assume the test is something an owner can run with an instrument bought online. It is not. NICEIC is clear that an EICR involves specialised tests and equipment and should never be a DIY job.[2]NICEIC, Electrical Installation Condition Reports (EICRs)

The bottom line

An insulation resistance test checks that the insulation around your wiring is intact. The minimum value is 1 megohm, and anything lower is recorded on the report with a code. It is one of the standard tests in an EICR and in the certification of new work, and it needs a competent electrician. You can see how we test on our EICR testing page.

Common questions

Why is it called a megger test?

It is the name the trade uses. The IET says insulation resistance testing is more commonly known as megger testing.

What is the minimum insulation resistance reading?

The IET gives 1 megohm as the minimum value used in BS 7671 today. A measured value below 1 megohm does not meet the standard and should be given a classification code.

Is an insulation resistance test dangerous?

It is carried out by a competent electrician with the right instrument. The IET lists only supply earth loop impedance, supply polarity and RCD testing as the live tests in a typical domestic check.

Can I do an insulation resistance test myself?

No. NICEIC says an EICR involves specialised tests and equipment and should never be a DIY job. If you suspect damaged wiring, ask a registered electrician to inspect it.

Sources

We cite the original source for every fact: legislation, GOV.UK, HSE, the IET, registration bodies and manufacturers' own documents. Each one shows the date we last checked it.

  1. Institution of Engineering and Technology (IET). History of insulation resistance testing (Wiring Matters, July 2020). Checked 11 November 2026. ↩
  2. NICEIC. Electrical Installation Condition Reports (EICRs). Checked 11 November 2026. ↩
  3. Institution of Engineering and Technology (IET). Implications of BS 7671:2018+A4:2026 on an EICRs (Wiring Matters, July 2026). Checked 11 November 2026. ↩
  4. Institution of Engineering and Technology (IET). Minimizing unnecessary live testing for initial verification (Wiring Matters, May 2025). Checked 11 November 2026. ↩

Where this matters

EICR testing

Related terms