Glossary · Testing, inspection and certificates
Key points
- It checks wires are properly connected, with no unintended breaks or unnecessarily high resistance at joints and terminations.
- Protective conductor continuity is tested on circuits. Live conductor continuity is tested on ring final circuits.
- R1 plus R2 is the combined resistance of the line and protective conductors, found with dead testing.
- It is one of the dead tests, so it avoids touching live parts, which keeps the work safer for the electrician.
- It needs specialist instruments. NICEIC says an EICR should never be a DIY job.
How a continuity test works
Electricity needs a complete path. A continuity test checks that the conductors in a circuit give that path, with nothing broken or badly connected along the way. NICEIC describes it as a check that all wires are properly connected, with no unintended breaks or unnecessarily high resistance at joints and terminations.[1]NICEIC, Electrical Installation Condition Reports (EICRs)
It is one of the circuit tests in an EICR. The others are insulation resistance, polarity, earth fault loop impedance and RCD testing, and NICEIC lists continuity first.[1]NICEIC, Electrical Installation Condition Reports (EICRs) Our page on what an EICR tests shows where it fits.
A loose or corroded joint can have high resistance. That matters because the earth conductor must carry fault current if something goes wrong. If it is broken or high in resistance, protection that relies on it may not work as intended. Electrical Safety First lists a lack of earthing or bonding among the things periodic inspection looks for.[3]Electrical Safety First, Periodic Inspection and Testing
What gets tested
| Test | What it checks |
|---|---|
| Continuity of protective conductors | The earth conductor of each circuit is unbroken and well connected |
| Continuity of live conductors on ring circuits | The live conductors of a ring final circuit form a complete loop. See ring main vs radial |
| R1 plus R2 | The combined resistance of the line conductor (R1) and the circuit protective conductor (R2) |
The IET’s list of the minimum tests for a typical home with an RCBO on each circuit includes continuity of the protective conductor and continuity of the live conductors for ring final circuits.[2]Institution of Engineering and Technology (IET), Minimizing unnecessary live testing for initial verification (Wiring Matters, May 2025) The IET says R1 plus R2 is determined by dead testing, and that this reduces the need to reach live terminals. It can also help verify polarity.[2]Institution of Engineering and Technology (IET), Minimizing unnecessary live testing for initial verification (Wiring Matters, May 2025)
R1 plus R2 has a second use. The IET says adding it to the measured external earth fault loop impedance, Ze, gives the circuit’s earth fault loop impedance. Downstream of an RCD, the IET also says continuity of the protective conductors can be enough to confirm protection.[2]Institution of Engineering and Technology (IET), Minimizing unnecessary live testing for initial verification (Wiring Matters, May 2025)
Example
Karen’s house in Kirkstall has a ring circuit feeding the downstairs sockets. During her EICR the electrician tests the continuity of the ring’s live conductors and of its protective conductor. In a ring, a break in the loop does not always stop the sockets working, because the circuit can still be fed from one end. That is why the continuity test is done rather than relying on the sockets working. The electrician records the readings on the schedule of test results and notes any observation on the report.
What people get wrong
Many people think that if every socket works, the wiring must be fine. A continuity test proves something different: that every conductor is complete and well connected. A socket can work while its earth connection is poor or its ring is broken at one point.
The second mistake is thinking this is a test an owner could do with a cheap meter. It needs specialist instruments and a competent person, and NICEIC says an EICR should never be a DIY job.[1]NICEIC, Electrical Installation Condition Reports (EICRs)
The bottom line
A continuity test checks that your circuit conductors are complete and well connected, especially the earth conductor and the live conductors on a ring circuit. It is done with the circuit isolated and feeds into other tests such as earth fault loop impedance. Ask your electrician which circuits were covered when you read your EICR. Our EICR testing page explains how we report.
Common questions
What is a continuity test for?
It confirms that conductors are properly connected end to end, with no breaks and no high resistance at joints. NICEIC lists it as the first of the circuit tests carried out in an EICR.
What is R1 plus R2?
R1 is the resistance of the line conductor and R2 is the resistance of the circuit protective conductor. Added together they are found by dead testing and used to work out earth fault loop impedance.
Why are ring circuits tested differently?
A ring final circuit also needs continuity of its live conductors tested, on top of the protective conductor, as the IET's list of minimum tests shows. That checks the ring is complete.
Is a continuity test done with the power on?
The IET describes R1 plus R2 as determined by dead testing, which means with the circuit isolated. The live tests in a typical home are different ones.
Sources
We cite the original source for every fact: legislation, GOV.UK, HSE, the IET, registration bodies and manufacturers' own documents. Each one shows the date we last checked it.
- NICEIC. Electrical Installation Condition Reports (EICRs). Checked 11 November 2026. ↩
- Institution of Engineering and Technology (IET). Minimizing unnecessary live testing for initial verification (Wiring Matters, May 2025). Checked 11 November 2026. ↩
- Electrical Safety First. Periodic Inspection and Testing. Checked 11 November 2026. ↩