Glossary · Wiring, circuits and faults
Key points
- A UK low-voltage supply is either TN-S, TN-C-S (also called PME) or TT, according to the IET.
- TT homes have no earth from the supplier and use their own earth electrode, often an earth rod, with RCD protection.
- PME earths the supply neutral at intervals and shares it as the earth. If that neutral breaks, metalwork can become live.
- Typical external earth fault loop impedance figures quoted by the IET are 0.8 ohm for TN-S, 0.35 ohm for TN-C-S and 21 ohm for TT.
- Your electrician or the network operator identifies your system. You cannot reliably tell from the outside.
How earthing systems work
Every installation needs a path for fault current to return safely to the source, so the protective device switches off quickly. The earthing system describes where that path comes from. The IET says the supply will be TN-S, TN-C-S (PME) or TT, and that the distributor can tell you which.[1]IET, Earthing: your questions answered In the names, T means earth (from the French terre), N means neutral, S means separate and C means combined.[1]IET, Earthing: your questions answered
The three systems compared
| System | Where the home’s earth comes from | What to know |
|---|---|---|
| TN-S | A separate earth conductor from the supplier, typically the metal sheath or armour of the service cable | Neutral is earthed at the source only |
| TN-C-S (PME) | The supplier’s neutral, which also acts as earth | Neutral is earthed at the source and at intervals |
| TT | An earth electrode installed at the home | No earth facility from the supplier |
The IET explains each. In TN-S the neutral of the source is earthed at one point only, near the source, and the consumer’s earth terminal is typically connected to the metallic sheath or armour of the distributor’s service cable.[1]IET, Earthing: your questions answered In TN-C-S the supply neutral is connected to earth at the source and at intervals along its run, usually called protective multiple earthing (PME). The distributor’s neutral also returns earth fault current to the source, and the distributor provides a consumer’s earth terminal linked to the incoming neutral.[1]IET, Earthing: your questions answered In TT there is no earth facility from the distributor, so the consumer must provide an earth electrode.[1]IET, Earthing: your questions answered
Earth rods and TT
A TT earthing facility is installed when the distributor does not provide a TN system or when one cannot be used.[3]IET, TT earthing considerations The electrode can be an earth rod or pipe, tape, plate or buried metalwork, and the IET says a rod is a simple and usually the most cost-effective choice.[3]IET, TT earthing considerations
A TT system has a higher external loop impedance, which does not give enough fault current to operate fuses or circuit breakers within the required time, so an RCD must be used for shock protection.[3]IET, TT earthing considerations See our guide to earth fault loop impedance. Soil conditions matter. The IET says freezing greatly raises resistance, so a TT electrode needs periodic inspection and testing, and ideally at different times of year.[3]IET, TT earthing considerations
The PME risk and the supply fault
In PME, the shared neutral can be broken. The IET warns that if the distributor’s combined neutral and earth conductor breaks, diverted neutral currents and dangerous touch voltages can appear on metalwork connected to the home’s earth terminal. Outdoor taps and Class I equipment are examples, and the risk of shock is greater for people outdoors who are in contact with the ground.[2]IET, Broken PEN That is why bonding on PME homes is more onerous, as covered under protective bonding, and why the 2020 amendment to BS 7671 added methods of protection against an open-circuit supply neutral for EV charging. See PEN fault and open PEN devices.[2]IET, Broken PEN
The IET also says PME is not provided for places such as caravans, boats and fuel filling stations, and that TT is a good solution when PME risks are unacceptable.[2]IET, Broken PEN
Typical values
The IET quotes typical external earth fault loop impedances declared by the distributor: 0.8 ohm for TN-S, 0.35 ohm for TN-C-S and 21 ohm for TT. It stresses these are typical only and will differ when tested on site.[4]IET, BS 7671 FAQs - Earthing and Bonding
Example
Sandeep is adding an outside socket at his house in Cookridge. His electrician first identifies the earthing system, because the answer affects the protection needed outdoors. The electrician checks the supply arrangement and tests before quoting. Sandeep learns that the earthing type is part of the design, not a detail.
What people get wrong
Many people assume a separate earth wire at the meter means TN-S. The IET says an installer should presume a supply with a separate protective conductor is TN-C-S unless the distributor confirms TN-S in writing.
That guidance comes from the IET’s article on broken supply neutrals.[2]IET, Broken PEN The second mistake is thinking TT is a lesser system. The IET describes it as safe and effective when designed and tested properly.[3]IET, TT earthing considerations
The bottom line
A UK home is earthed in one of three ways: a separate cable earth (TN-S), the supplier’s neutral (TN-C-S or PME) or its own earth rod (TT). The system sets the protection and bonding the home needs. Ask the network operator or a registered electrician which you have, and leave any change to an earth electrode to them.
Common questions
How do I find out which earthing system I have?
The IET says the distributor, the company that runs your local network, can provide this information. A registered electrician can also identify it on site. The IET also says that a supply with a separate protective conductor should be presumed to be TN-C-S unless the distributor confirms TN-S in writing.
What is PME?
Protective multiple earthing is a form of TN-C-S. The supplier connects the supply neutral to earth at the source and at intervals along its run, and provides the home's earth terminal linked to the incoming neutral. The IET describes the S as the separation of neutral and earth on the installation side.
What is an earth rod for?
An earth rod is one way to make an earth electrode, which a TT installation needs because the supplier provides no earth. The IET says it is a simple and usually the most cost-effective method, but not suitable for every site.
Is TT earthing worse?
No. The IET calls TT a safe and effective method that can be a good solution where PME risks are unacceptable. It needs RCD protection and periodic testing, because soil conditions change with the weather.
Sources
We cite the original source for every fact: legislation, GOV.UK, HSE, the IET, registration bodies and manufacturers' own documents. Each one shows the date we last checked it.